What Is the Purpose of Tap Changers?

Tap changers are essential components in power transformers, designed to regulate voltage and maintain power quality in electrical systems. By adjusting the transformer winding ratios, tap changers allow voltage control without interrupting the power supply. This document explores the purpose, types, and operational significance of tap changers in modern transformer applications.


What Does a Tap Changer Do in a Transformer?

Transformers must adapt to fluctuating voltage conditions caused by varying load demands, grid disturbances, and distance from power sources. Without compensation, these changes can cause under-voltage or over-voltage, damaging equipment or reducing performance. A transformer without voltage regulation capability must either be oversized or paired with external devices—both costly and inefficient. That's where tap changers come in: they allow voltage fine-tuning directly at the transformer, ensuring steady delivery to end users.

A tap changer adjusts the transformer's output voltage by changing the turns ratio of its windings. It does this by selecting different "taps" on the winding—connection points along the coil that represent varying numbers of turns—thereby regulating the output voltage to compensate for load or supply variations. There are two main types: off-load tap changers (OLTC), which require the transformer to be de-energized before adjustment, and on-load tap changers (OLTC), which allow automatic or remote adjustment during normal operation without interrupting power.

Tap changers are essential for grid reliability, voltage regulation, and system efficiency in both utility and industrial transformers.

Tap changers change the voltage by adjusting the number of winding turns in use.True

Each tap corresponds to a specific point on the coil, and switching between them alters the transformer's turns ratio.

On-load tap changers can be adjusted while the transformer is energized.True

OLTCs are designed to switch taps under load without disrupting the power supply using arc suppression techniques.

All transformers must have on-load tap changers.False

Many smaller distribution transformers use off-load tap changers or fixed-ratio windings, depending on their voltage regulation needs.


1. Understanding Tap Changer Operation

A transformer's voltage ratio is proportional to the number of turns in the primary and secondary windings:

$$
V_s = V_p \times \frac{N_s}{N_p}
$$

  • Taps are points along the winding where conductors are brought out and connected to a switch.
  • By selecting a tap with more or fewer turns in use, the effective ratio changes, allowing output voltage to be increased or decreased in steps (typically ±5% to ±20%).

2. Off-load vs. On-load Tap Changers (OLTCs)

FeatureOff-load Tap Changer (NLTC)On-load Tap Changer (OLTC)
Adjustment requires power off✔️ Yes❌ No
Suitable forDistribution transformersTransmission & HV transformers
Adjustment frequencyInfrequent (manual)Continuous/automatic
Typical voltage range±5% to ±10%±10% to ±25% in 16–33 steps
Arc suppressionNot requiredEssential (vacuum, resistor, reactor)
Control typeManual/mechanicalMotorized, automatic, remote-controlled

🔌 OLTCs use diverter switches, arcing contacts, and transition resistors/reactors to prevent short-circuits or voltage spikes during switching.


3. Tap Changer Placement and Design

Tap changers are usually installed on the high-voltage (HV) winding side, where:

  • Current is lower, reducing stress on contacts
  • Voltage steps are larger, offering better control
Tap LocationDescription
HV WindingMost common, reduces component size and complexity
Midpoint/center of windingMinimizes voltage stress across insulation
Series or phase-wound tapsUsed in complex autotransformer designs

🛠 Designs vary by transformer type, voltage class, and regulatory requirements.


4. Voltage Regulation Use Case Example

Transformer rated: 33 kV / 11 kV with ±10% OLTC (in 17 steps)

Tap PositionOutput Voltage
-89.9 kV
0 (Nominal)11.0 kV
+812.1 kV

This flexibility allows grid operators to:

  • Compensate for line voltage drops during peak demand
  • Maintain stable downstream voltage under variable loads
  • Optimize transformer efficiency and loading

5. Tap Changer Construction Overview

ComponentFunction
Selector SwitchConnects to desired tap on winding
Diverter SwitchTransfers load current without interruption
Transition Resistor/ReactorLimits circulating current during tap change
Drive MechanismElectric motor or manual gear
Control SystemMonitors voltage and automates tap selection
Oil Compartment (for OLTC)Separate from main tank; includes oil for arc suppression and cooling

🧪 Many modern OLTCs are enclosed in vacuum interrupters for maintenance-free operation and arc-free switching.


6. Automatic Voltage Regulation (AVR)

An AVR relay interfaces with the OLTC to:

  • Monitor secondary voltage
  • Compare with set reference
  • Command tap changes when voltage deviates beyond threshold
  • Operate with dead-band, time delay, and step logic
AVR FeatureFunction
Dead BandPrevents unnecessary tap changes for minor fluctuations
Step DelayPrevents rapid tap switching
Reverse Power BlockingDisables tap changes during load reversal

📡 OLTCs with AVRs are critical for smart grid integration, renewables, and voltage control loops.


7. Tap Changer Monitoring and Maintenance

AspectOLTCOLTC with Vacuum
Oil ConditionNeeds regular testingNo oil (sealed unit)
Contact WearRegular inspectionLong-life contacts
Timing MechanismShould be calibratedElectronic diagnostics available
SensorsOil temperature, position encoder, motor torque

Modern tap changers may include:

  • Condition monitoring sensors
  • Digital tap position encoders
  • Predictive maintenance analytics

8. Advantages and Limitations

AdvantageNotes
Voltage RegulationMaintains stable supply
Grid FlexibilitySupports varying load profiles
Energy OptimizationReduces system losses
Automation-ReadyIntegrates with SCADA, PLCs
LimitationNotes
Complex MechanismEspecially in OLTCs; needs precise control
Maintenance NeedsDiverter contacts and oil (unless vacuum-based)
CostIncreases upfront investment in high-voltage applications

What Are the Types of Tap Changers?

In voltage-regulated transformer systems, tap changers allow operators to fine-tune the turns ratio by switching to different winding taps. However, not all tap changers are created equal. Choosing the wrong type—manual instead of automated, or oil-based instead of vacuum-sealed—can lead to voltage instability, excessive maintenance, or even arcing faults under load. Therefore, it's critical to understand the different types of tap changers, their operating principles, and where each is best applied to maintain safe, efficient voltage regulation.

There are two main categories of transformer tap changers: Off-load Tap Changers (NLTC) and On-load Tap Changers (OLTC). Off-load types require the transformer to be de-energized for adjustment, making them suitable for fixed-ratio transformers or infrequent regulation. On-load tap changers operate while the transformer is energized and can adjust voltage under full load. Within OLTCs, further types exist based on transition technique: resistor-type, reactor-type, and vacuum-type. Each type has specific applications, maintenance profiles, and cost implications.

Choosing the correct tap changer ensures reliable voltage delivery, minimizes arc damage, and supports grid dynamics and automation.

Off-load tap changers require power to be disconnected before adjustment.True

NLTCs are mechanically simple and cannot safely switch current under load due to lack of arc suppression.

On-load tap changers can regulate voltage while the transformer is in service.True

OLTCs use diverter switches, resistors, or vacuum interrupters to safely make transitions under energized conditions.

All OLTCs use vacuum interrupters.False

While many modern OLTCs use vacuum technology, traditional models use oil-immersed resistors or reactors for arc suppression.


1. Off-Load Tap Changer (NLTC / De-energized Tap Changer)

FeatureDescription
OperationManual or motorized, only when transformer is offline
Use CaseDistribution transformers, cost-sensitive applications
Voltage RangeTypically ±5% or ±10%, 3–5 fixed steps
MechanismSimple rotary switch or tap links
LocationUsually on high-voltage winding side
ProtectionNo arc suppression needed

Advantages:

  • Economical
  • Mechanically simple
  • Maintenance-free

Limitations:

  • Inflexible during live operations
  • Not suitable for dynamic grid voltage control

2. On-Load Tap Changer (OLTC)

These operate under load conditions, allowing for voltage regulation without interrupting the power supply. Widely used in power transformers and HV substations.

a) Resistor-Type OLTC

| Mechanism | Two selector switches + diverter switch + resistors |
| Transition Type | Make-before-break via transition resistors |
| Arc Suppression | Resistors absorb arc energy |
| Application | Widely used in transmission transformers (≤245 kV) |
| Medium | Oil or vacuum insulated |

Advantages:

  • Robust design
  • Proven long-term performance

Drawbacks:

  • Arcing can degrade oil over time
  • Resistor heating limits switching frequency

b) Reactor-Type OLTC

| Mechanism | Uses a center-tapped reactor instead of resistors |
| Transition Type | Reactor limits circulating current between taps |
| Arc Suppression | Continuous current path avoids open contacts |
| Application | Older designs; rare in modern installations |
| Medium | Oil-immersed only |

Advantages:

  • Low energy dissipation
  • Longer switching life under moderate load

Drawbacks:

  • Complex mechanics
  • Requires larger compartment
  • Less commonly used today

c) Vacuum-Type OLTC

| Mechanism | Vacuum interrupters in diverter switch |
| Transition Type | Arc quenched in vacuum (no oil contamination) |
| Arc Suppression | Clean and reliable |
| Application | Modern designs, especially in dry-type transformers or sensitive grids |
| Medium | Vacuum-sealed interrupters + dry compartment or oil (hybrid designs) |

Advantages:

  • Virtually maintenance-free
  • No oil degradation
  • Clean, environmentally safer
  • Compact

Limitations:

  • Higher initial cost
  • May require external diagnostics or drive systems

📌 Most modern OLTCs adopt vacuum switching technology to eliminate the need for oil maintenance.


3. Comparison Table: Tap Changer Types

TypeEnergized SwitchingArc SuppressionInsulation MediumMaintenance NeedsCommon Use
Off-load (NLTC)❌ NoNot requiredAir/oilVery lowDistribution transformers
Resistor OLTC✔️ YesResistorsOilHigh (oil checks, contact wear)Transmission, substations
Reactor OLTC✔️ YesReactorOilModerateLegacy HV systems
Vacuum OLTC✔️ YesVacuum interruptersDry or hybridVery lowModern power transformers, dry-type

4. Selector and Diverter Functions in OLTCs

  • Selector Switch: Connects to selected tap (no load carried)
  • Diverter Switch: Makes/breaks load current, synchronized with arc suppression device (resistor/reactor/vacuum)

Transition must:

  1. Avoid open-circuiting the winding
  2. Avoid short-circuiting adjacent taps
  3. Limit arc duration and energy

These components are isolated in a separate tap changer compartment for safety and easier oil management.


5. Digital and Motorized Drive Options

Modern tap changers are often automated, integrating:

  • Motor drive mechanisms
  • Digital tap position indicators
  • Remote SCADA integration
  • Automatic Voltage Regulator (AVR) interfaces

📡 Smart OLTCs are crucial for dynamic load balancing, voltage optimization, and renewable grid integration.


6. Special Types and Hybrids

TypeUse
Linear OLTCFixed incremental steps
Reversing OLTCBidirectional tap range (+/− steps)
Coarse–Fine Tap ChangersCombines large and small step ranges
Dual Voltage OLTCChanges output and tap range simultaneously
Tap-changer-less Electronic RegulationSolid-state switching for fast, arc-free voltage control (emerging tech)

Why Is Voltage Regulation Important in Power Systems?

In any modern power system, voltage must remain within tight tolerances to ensure the safe and efficient operation of electrical equipment. Yet in practice, voltage can fluctuate due to load variability, distance from substations, transformer inefficiencies, and distributed generation, leading to costly consequences. Poor voltage regulation causes overheating, flickering, equipment damage, and even grid-wide instability. Maintaining precise voltage levels across transmission and distribution networks is not just about performance—it’s about reliability, safety, and energy efficiency at scale.

Voltage regulation is crucial in power systems to maintain consistent voltage levels across varying load and supply conditions. It ensures that the voltage delivered to end-users remains within specified limits (typically ±5% of nominal), despite fluctuations in demand or network configuration. Proper regulation protects sensitive equipment, reduces energy losses, improves power quality, and supports system stability. Voltage regulation is achieved using transformer tap changers, automatic voltage regulators (AVRs), capacitor banks, and reactive power compensation systems.

Without reliable voltage regulation, both utilities and consumers face increased operating risks and costs.

Voltage regulation maintains the voltage within acceptable limits despite load changes.True

Loads draw variable current, which can cause voltage drops or surges unless regulated.

Unregulated voltage can lead to transformer burnout and equipment failure.True

Voltage that deviates beyond tolerances causes thermal stress, insulation breakdown, and premature aging.

Voltage regulation is only necessary for high-voltage transmission systems.False

Voltage must be regulated at every level—from generation to distribution—to ensure consistent delivery to end-users.


1. What Is Voltage Regulation?

Voltage regulation is defined as the ability of a system to maintain a constant output voltage regardless of:

  • Load current variations
  • Supply-side disturbances
  • Switching operations or fault conditions

$$
text{Voltage Regulation (\%)} = \left( \frac{V{\text{no-load}} - V{\text{full-load}}}{V_{\text{full-load}}} \right) \times 100
$$

Where:

  • $V_{\text{no-load}}$: Voltage with no current drawn
  • $V_{\text{full-load}}$: Voltage under rated load

Target voltage regulation is typically:

  • < ±5% for residential and commercial
  • < ±2.5% for sensitive industrial systems

2. Why Voltage Deviates: Real-World Causes

CauseEffect on Voltage
High load demandVoltage drop due to line impedance
Light loadingVoltage rise (Ferranti effect in transmission)
Reactive power imbalanceOver or under voltage
Distance from substationVoltage sags with resistance and inductance
Renewable integrationSudden injection/withdrawal of voltage (PV, wind)

📉 These deviations can create unsafe conditions, especially in sensitive electronics, motors, and industrial drives.


3. Consequences of Poor Voltage Regulation

SectorImpact
IndustrialMotor burnout, PLC failure, production downtime
ResidentialAppliance damage, flickering lights, low efficiency
UtilityOverloading transformers, grid instability, customer complaints
Renewable PlantsGrid code violations, inverter tripping

🧯 Over-voltage can cause insulation failure and arcing
💡 Under-voltage causes inefficient operation, overheating, and frequent restarts


4. How Is Voltage Regulated in Power Systems?

a) Transformer Tap Changers (Manual or On-load)

  • Adjust the winding turns ratio to raise/lower voltage
  • OLTCs adjust voltage dynamically based on load
  • Widely used in HV/MV substations

b) Automatic Voltage Regulators (AVR)

  • Senses secondary voltage
  • Controls tap changer position or boost devices
  • Programmable with deadband, delay, and step size

c) Capacitor Banks & Reactors

  • Inject or absorb reactive power
  • Maintain voltage stability by adjusting power factor
  • Used in distribution feeders and substations

d) Static VAR Compensators (SVC) & STATCOMs

  • Fast, dynamic voltage control for transmission grids
  • Use thyristor-based or IGBT-controlled switching
DeviceVoltage Regulation CapabilitySpeed
OLTC±10–25%Seconds
AVR±2–10%Instant (with OLTC)
Capacitor BankFixed or switchedMinutes
STATCOM±5–10%Milliseconds

5. Voltage Regulation in Distribution Networks

TechniqueApplication
Feeder voltage regulatorsMid-line correction in long rural feeders
Step voltage regulators (SVR)Pole-mounted units that boost voltage
Line drop compensationAVR adjusts taps based on current and distance
Smart grid automationSynchronized regulation across DERs and loads

📈 Modern systems employ adaptive regulation strategies based on load forecasting, SCADA data, and grid analytics.


6. Case Study: Industrial Facility with Poor Voltage Regulation

Scenario: 11 kV industrial feeder, 2.5 km from substation

SymptomCauseFix
Voltage drop of 6% at peak loadHigh feeder impedanceAdd OLTC at distribution transformer
Frequent tripping of VFDsVoltage sags on motor startAdd capacitor bank + AVR
Product rejection due to heatPoor regulation in heating controlInstall line regulator with real-time control

Result: After implementing tap changers and reactive compensation, voltage variation reduced from ±6% to ±1.5%, improving uptime and product quality.


7. Voltage Regulation and Energy Efficiency

FactorBenefit
Stable voltageReduces copper losses in motors and cables
Optimized power factorImproves kVA utilization
Minimized transformer overloadingExtends service life
Reduced rework or wastageIn manufacturing systems

📊 A 3% voltage drop can cause up to 8–10% increase in motor current, leading to faster overheating.


8. Grid Codes and Voltage Tolerances

Country/StandardVoltage Tolerance
IEC 60038±5% (LV), ±10% (MV/HV)
ANSI C84.1Service voltage ±5%
EN 50160±10% for LV, ±7% for MV
IEEE 1159 (Power Quality)Defines sag/swell thresholds

Grid operators must comply with these limits or face:

  • Penalties
  • System losses
  • Equipment failures

Where Are Tap Changers Commonly Used?

As power networks grow more complex and sensitive to load variability, voltage regulation becomes mission-critical. Tap changers—whether on-load or off-load—serve as integral components in transformers that require precise voltage control, especially under dynamic conditions. Whether in high-voltage substations, industrial processing plants, or renewable energy projects, tap changers are used wherever transformers must adapt to changing grid or load conditions without sacrificing voltage stability.

Tap changers are commonly used in high-voltage power transformers at transmission and substation levels, distribution transformers in utility feeders, industrial control transformers, renewable energy interconnection transformers, and mining or remote-site transformers. These applications rely on tap changers to regulate voltage output, compensate for load variations, and maintain system stability. On-load tap changers (OLTCs) are employed where voltage must be adjusted under energized conditions, while off-load tap changers (NLTCs) are used in systems with infrequent voltage changes.

Their adaptability ensures continuous operation, voltage compliance, and equipment protection across energy-intensive industries.

Tap changers are widely used in substation and transmission transformers for grid voltage regulation.True

OLTCs in substations adjust winding ratios to regulate voltage without interrupting service.

Tap changers are not used in renewable energy transformers.False

Tap changers are used in wind, solar, and hydro transformers to manage fluctuating generation and ensure grid voltage compliance.

Industrial transformers with variable load often benefit from OLTCs or programmable tap changers.True

In dynamic industrial settings, automated tap changers help maintain power quality despite shifting load profiles.


1. High-Voltage Transmission Transformers

Tap changers are critical in bulk power transmission systems to:

  • Regulate grid-side voltage (±10–25%)
  • Adjust for daily load curves
  • Enable interconnected grid balancing
FeatureDescription
LocationGrid substations, interconnection points
Voltage Class110 kV – 765 kV
Tap Changer TypeOn-load (OLTC), typically resistor or vacuum type
ControlSCADA integrated, automatic voltage regulators (AVRs)

📡 These transformers help maintain uniform voltage across transmission corridors, supporting national grid codes and stability.


2. Distribution Substations and Utility Feeders

Tap changers in medium-voltage transformers (typically 33 kV / 11 kV) manage:

  • Voltage drops along long rural feeders
  • Load balancing between urban and industrial zones
  • Day-night demand shifts
Common UseFeature
Urban substationsAutomatic OLTCs with smart grid control
Rural feedersStep voltage regulators (SVRs) on poles
Pad-mounted unitsOff-load tap changers for occasional tuning

These units ensure end-of-line voltage stays within ±5% for residential and commercial reliability.


3. Renewable Energy Integration (Wind, Solar, Hydro)

With fluctuating output, renewable generation needs constant voltage alignment to avoid grid rejection:

ApplicationTap Changer Role
Wind farm collector transformersMaintain voltage during wind variation
Solar inverter step-up transformersCompensate for irradiance-induced drops
Hydro step-up transformersAlign generator output with HV grid levels

Often equipped with OLTCs + voltage automation to adapt instantly to dynamic power injection.

📊 Voltage variation of ±10% is typical in renewable plants; tap changers reduce this to ±2%.


4. Industrial Facilities and Large Loads

Industries like steel, cement, mining, and chemical processing have large motors and fluctuating loads. Tap changers here:

  • Maintain motor voltage during start-up or torque peaks
  • Regulate voltage for resistive loads (heaters, furnaces)
  • Reduce downtime due to under/overvoltage faults
SetupTap Changer Type
6.6 kV / 11 kV process plant transformersOLTC with AVR
HVAC/load centers in data centersNLTC with remote control
Motors >500 kWOLTC for smooth torque delivery

These tap changers can be remotely adjusted or programmed based on production cycle.


5. Railways and Traction Transformers

Tap changers in traction substations regulate:

  • Voltage for 25 kV or 15 kV railway lines
  • Ensure stability during train starts/stops
  • Synchronize with regenerative braking surges

OLTCs help manage:

  • Frequent load shifts
  • Voltage harmonics
  • Substation-to-substation coordination

🚄 Real-time tap changes prevent flicker and ensure constant train performance.


6. Remote and Harsh-Environment Transformers

In locations like:

  • Oil fields
  • Offshore wind farms
  • Mining operations
  • Isolated villages

Tap changers enable:

  • Manual voltage setting with NLTC
  • Autonomous OLTC operation using local voltage sensing
  • Rugged designs (epoxy insulation, sealed enclosures)
Tap TypeEnvironment
NLTC (air-insulated)Stable remote grid
OLTC (vacuum-sealed)Critical off-grid systems with variability

These transformers support self-contained microgrids and mission-critical sites.


7. Building Power Systems & Hospitals

Large commercial buildings and healthcare facilities use tap changers in:

  • Main incoming service transformers (33/11 kV or 11/0.415 kV)
  • Internal voltage regulation for medical/lab equipment
  • Backup generator-to-grid interfacing

Key features:

  • Smart AVR + OLTC combos
  • Low-voltage step-up transformers with NLTC
  • Surge protection coordination

⚕️ Hospitals especially require tight voltage stability for imaging, sterilization, and IT systems.


8. Emerging Use: Smart Grid Automation

In smart grids, tap changers:

  • Interact with real-time load forecasting
  • Adjust based on voltage profiles and consumption analytics
  • Operate in coordinated groups to prevent overcompensation
FeatureBenefit
Coordinated OLTCsAvoid voltage oscillation in looped feeders
Edge intelligenceLocal tap decisions based on IoT sensors
Digital twin simulationOptimize tap settings across the network

🔌 Tap changers are no longer just mechanical devices—they are now part of the grid intelligence ecosystem.


Summary Table: Where Tap Changers Are Used

SectorVoltage LevelTap Changer TypePurpose
Transmission Substations110–765 kVOLTCGrid voltage stability
Distribution Feeders11–33 kVOLTC, NLTCLoad-side voltage control
Renewable Energy33–132 kVOLTCInjection control, grid compliance
Industrial Plants6.6–33 kVOLTC, NLTCEquipment protection
Mining/Oil & GasAnyOLTC/NLTCAutonomous voltage adjustment
Commercial Buildings0.415–11 kVNLTCLoad center voltage tuning

Conclusion

Tap changers are crucial for maintaining consistent voltage levels in transformers under varying load conditions. Whether through manual or automatic adjustment, they play a key role in enhancing transformer adaptability, system reliability, and energy quality. Understanding their function helps in designing more robust and flexible power infrastructure.


FAQ

Q1: What is the primary purpose of a tap changer in a transformer?
A1: The main purpose of a tap changer is to regulate the output voltage of a transformer by adjusting the number of turns in the winding. This compensates for:

Voltage drops due to load changes

Fluctuations in supply voltage
It ensures the output remains within acceptable voltage limits, protecting connected equipment and maintaining power quality.

Q2: What are the two main types of tap changers?
A2: Off-Load Tap Changer (OLTC):

Can only be operated when the transformer is de-energized

Typically used in distribution transformers with infrequent voltage adjustments

On-Load Tap Changer (OLTC):

Allows tap changes while the transformer is energized and under load

Common in power and transmission transformers

Enables automatic voltage regulation (AVR) through motor-driven or electronic control

Q3: How does a tap changer adjust voltage?
A3: Tap changers alter the number of effective turns in the transformer's winding, changing the turns ratio and hence the output voltage:

Increasing tap: Raises the number of turns → lowers output voltage

Decreasing tap: Reduces the number of turns → raises output voltage
Tap positions are typically marked as +5 to -5 or more steps, each giving a small voltage adjustment (e.g., ±1.25%).

Q4: Why are tap changers critical for power system stability?
A4: Tap changers ensure voltage stability, which is vital for:

Protecting sensitive electrical equipment

Maintaining consistent service during fluctuating loads

Ensuring reactive power balance in transmission systems
Without proper tap regulation, networks face voltage sags, swells, or imbalance, leading to equipment malfunction or system failures.

Q5: How is a tap changer maintained or monitored?
A5: OLTCs require regular oil analysis, contact inspection, and timing tests due to mechanical wear

Smart tap changers include sensors and controllers for condition monitoring and fault detection

Digital tap position indicators and SCADA integration are used for remote operation in modern systems
Timely maintenance extends tap changer life and improves transformer reliability.

References

Electrical4U: Tap Changer in Transformer
https://www.electrical4u.com/tap-changer-in-transformer/

IEEE C57.131-2021: Guide for Tap Changers
https://standards.ieee.org/standard/C57_131-2021.html

Doble Engineering: Tap Changer Diagnostics
https://www.doble.com/solutions/tap-changer-testing/

NREL: Voltage Regulation in Grid Transformers
https://www.nrel.gov/docs/fy21osti/tap-changer-transformers.pdf

ScienceDirect: Tap Changer Function in Smart Grids
https://www.sciencedirect.com/science/article/pii/S2352484720301087

Tags:

Picture of Norma Wang
Norma Wang

Focus on the global market of Power Equipment. Specializing in international marketing.

Get Support Now

Get a Quote / Support for Your Project

  • Don’t worry, we hate spam too!