What are Common Transformer Faults and Their Causes?

Transformers are critical components in power systems, but like all electrical equipment, they are susceptible to faults. Understanding common transformer faults and their causes is essential for maintaining system reliability, reducing downtime, and preventing costly failures. These faults may result from electrical, thermal, mechanical, or environmental stresses, and early detection is key to minimizing their impact.


What Are the Most Common Electrical Faults in Transformers?

Transformers are vital to every stage of the power system—from generation to distribution—and any electrical fault within a transformer can lead to catastrophic failure, power outages, equipment damage, or even fire. Whether due to insulation breakdown, overvoltage, or short-circuit conditions, these faults must be detected and addressed swiftly. Knowing the most common electrical faults in transformers is essential for preventive maintenance, condition monitoring, and long-term asset protection.

The most common electrical faults in transformers include winding short circuits (inter-turn or phase-to-phase), insulation breakdown, earth (ground) faults, partial discharges, external short circuits, and open circuit faults. These issues can arise from aging, thermal stress, overvoltage surges, contamination, or manufacturing defects, and require timely detection through protective relays, diagnostic testing, and online monitoring systems.

This article identifies and explains the nature, causes, detection methods, and risks of typical transformer electrical faults—empowering engineers and operators to act before failure occurs.

Transformer faults such as winding shorts, ground faults, and insulation breakdowns are common and can be detected with proper monitoring and protection systems.True

These faults are well-documented in field operations and can be predicted or mitigated through diagnostic tests and protection relays.

Transformers do not typically experience electrical faults unless subjected to deliberate damage.False

Normal aging, thermal cycling, environmental stress, and load fluctuations can all cause electrical faults in transformers.


1. Winding Short Circuit Faults

TypeDescription
Inter-turn short circuitTwo adjacent turns in the same winding short
Phase-to-phase faultWindings of two phases short to each other
Layer or disc faultFault between layers or disc segments in winding

Causes:

  • Insulation aging
  • Dielectric oil degradation
  • Surge overvoltages
  • Manufacturing defects

Risks:

  • Localized heating, leading to thermal runaway
  • Core saturation and uneven magnetic fields
  • Severe mechanical stress during faults

Detection:

  • Differential protection relays
  • Sudden pressure relay
  • Dissolved Gas Analysis (DGA) showing acetylene, ethylene

2. Earth (Ground) Faults

ScenarioDescription
Primary or secondary winding touches grounded core or tankDangerous current path to ground

Causes:

  • Insulation failure
  • Water ingress into windings or bushings
  • Improper grounding configuration

Risks:

  • Core damage
  • Fire hazard
  • Potential for electric shock

Detection:

  • Restricted Earth Fault (REF) protection
  • Insulation resistance (IR) testing
  • Leakage current monitoring

3. Insulation Breakdown Faults

Fault TypeDescription
Solid insulation failurePaper or pressboard around windings degrades
Liquid insulation breakdownMineral oil loses dielectric strength (BDV)

Causes:

  • Overheating
  • Moisture contamination
  • Chemical aging
  • Excessive mechanical stress

Risks:

  • Flashover between winding layers
  • Arc formation and rapid fault escalation

Detection:

  • Oil dielectric breakdown test (BDV)
  • Tan delta/power factor testing
  • DGA showing CO, CO₂ (paper degradation)

4. Partial Discharge (PD) Faults

DefinitionLocalized electrical discharges that do not completely bridge electrodes

Causes:

  • Voids in insulation
  • Sharp edges or air bubbles
  • Manufacturing flaws

Risks:

  • Progressive insulation degradation
  • Precursor to catastrophic failure

Detection:

  • PD sensors
  • UHF/TEV testing
  • Online PD monitoring systems

PD is common in high-voltage transformers and requires ongoing surveillance.


5. External Short Circuit Faults

SituationFault occurs outside transformer but affects internal operation

Causes:

  • Downstream cable failure
  • Load-side equipment shorting
  • Grid fault propagating through busbars

Risks:

  • High fault current stress on windings and bushings
  • Mechanical damage from electrodynamic forces

Protection:

  • High-speed circuit breakers
  • Differential protection
  • Backup time-delayed overcurrent relays

6. Open Circuit Faults

TypeDescription
Broken winding connectionOpen in primary or secondary coil
Tap changer disconnectionOLTC contacts fail or open

Causes:

  • Mechanical damage
  • Loose terminal connections
  • Internal arcing

Risks:

  • Voltage instability
  • Load imbalance or system blackout

Detection:

  • Voltage and current mismatch detection
  • Transformer vector group test
  • OLTC position sensing alarms

Summary Table: Common Electrical Faults in Transformers

Fault TypeTypical CauseDetection Methods
Inter-turn short circuitInsulation failureDifferential protection, DGA
Phase-to-phase shortSurge or overheatingImpedance tests, relay tripping
Ground faultMoisture, aging insulationREF protection, insulation resistance test
Insulation breakdownOil degradationBDV test, power factor, DGA
Partial dischargeVoids, contaminantsPD sensors, UHF testing
External short circuitCable/grid failureCurrent transformers, high-speed relays
Open circuitLoose terminals, contact wearVoltage monitoring, tap changer status

How Do Thermal Faults Develop in Transformers?

Thermal faults are one of the most frequent and destructive failure modes in transformers. Whether caused by overload, poor cooling, insulation degradation, or internal arcing, these faults silently damage a transformer’s core, windings, and oil long before visible symptoms appear. If left undetected, they can lead to catastrophic failure, expensive repairs, fire hazards, and extended outages. Understanding how thermal faults develop—and how to detect them—is key to transformer health management.

Thermal faults in transformers develop when excessive heat is generated within the core, windings, tap changers, or insulation due to overloading, internal faults, cooling system failure, or poor ventilation. This heat accelerates insulation aging, reduces dielectric strength, causes oil breakdown, and can lead to hotspots, carbonization, or even internal arcing. Early signs of thermal faults can be detected through dissolved gas analysis (DGA), temperature sensors, infrared thermography, and real-time monitoring systems.

This article explores the mechanisms, causes, stages, and detection of thermal faults in power and distribution transformers—helping you prevent failures before they happen.

Thermal faults develop in transformers when internal components overheat due to overloading, insulation failure, or cooling issues.True

Overheating leads to degradation of insulation and oil, resulting in hotspots and increased risk of internal failure.

Transformers cannot develop thermal faults if they operate under rated load.False

Even within rated load, poor cooling, aging insulation, or oil contamination can lead to localized overheating and thermal faults.


1. What Are Thermal Faults in Transformers?

Thermal faults refer to any internal condition that causes excessive localized heating beyond the transformer’s design limits. These include:

  • Hotspots in windings or cores
  • Thermal runaways from poor heat dissipation
  • Arcing at contact points (e.g., tap changers)
  • Oil degradation and carbonization near heat zones

Even brief episodes of thermal stress can significantly reduce transformer life.


2. Primary Causes of Thermal Faults

CauseMechanism
OverloadingExcess current → I²R loss in windings = overheating
Cooling system failureFans/pumps not working → heat accumulation
High ambient temperatureReduces heat dissipation → oil and insulation strain
Blocked radiators/ventilationImpedes airflow → local temperature rise
Insulation agingLess heat resistance → faster degradation under heat
Tap changer contact resistancePoor contact = arcing and localized heating

Cumulative heat effects double insulation aging rate for every 6–8°C rise above nominal.


3. Stages of Thermal Fault Development

StageSymptoms and Impact
Early overheatingMinor oil temperature rise, slight gas generation
Hotspot formationLocalized high temperature in windings or tap area
Oil decompositionRelease of hydrocarbons (C₂H₆, CH₄, C₂H₂) in DGA
Insulation breakdownPaper turns brittle, lower dielectric strength
Carbon tracking and arcingLeads to internal arc fault or winding failure

Without intervention, a thermal fault progresses from mild degradation to a major dielectric failure.


4. Types of Thermal Faults by Temperature Range (IEEE C57.104)

Temperature (°C)Fault TypeTypical Gas Signature (in DGA)
<150Low-temperature heating (paper aging)CO, CO₂, minor CH₄
150–300Medium-temperature overheatingC₂H₄, CH₄, C₂H₆
300–700High-temperature overheatingC₂H₂ (acetylene), H₂, C₂H₄, CH₄
>700Arcing or hot spot faultHigh acetylene (C₂H₂), hydrogen (H₂)

Dissolved Gas Analysis (DGA) is the most effective method to pinpoint fault type and severity.


5. Common Zones of Thermal Faults

Transformer ZoneCommon Thermal Issues
WindingsOverheating due to high current or poor contacts
CoreCore lamination faults, flux imbalance
Tap changerContact arcing, resistive heating
Oil systemHot spots from poor circulation or sludge buildup
Bushing terminalsLoose connections and tracking

Most hotspots go undetected unless sensors or thermal imaging are in place.


6. Detection and Monitoring Techniques

MethodWhat It Detects
Oil temperature sensorsTop oil temp and rate of rise
Winding hot-spot sensorsLocal thermal stress points
Dissolved Gas AnalysisGases indicating thermal decomposition
Infrared thermographyExternal hotspots (bushings, radiators)
Online thermal modelsPredict hot-spot temperatures via algorithms

Smart transformers include real-time temperature diagnostics and alerting capabilities.


7. Impact of Thermal Faults on Transformer Life

EffectLong-Term Impact
Insulation breakdownAccelerated aging, risk of electrical failure
Oil sludging and acidityReduced cooling and dielectric strength
Bushing failureArcing, surface tracking, explosive failure
Increased core lossesEnergy inefficiency and overheating feedback

The IEEE defines normal insulation life at 110°C, but just a 10°C rise can halve transformer lifespan.


8. Preventing Thermal Faults

StrategyDescription
Load managementAvoid continuous operation above 80% capacity
Cooling system inspectionRegularly test fans, pumps, radiators
Oil analysis and filtrationRemove sludge and moisture, restore dielectric
Sensor integrationEnable real-time thermal alerts
Scheduled thermographic surveysIdentify loose connections and hotspots

Digital monitoring systems are now essential for early thermal anomaly detection.


Summary Table: Thermal Fault Development in Transformers

Fault CauseDetection MethodKey Risk
OverloadLoad logs, thermal sensorsInsulation burnout
Cooling failureFan/pump status, IR scansTop oil temperature spike
Insulation degradationDGA, power factor testDielectric collapse
Tap changer arcingContact analysis, DGALocalized flashover
External environmentWeather sensorsAmbient impact on cooling

What Mechanical Faults Can Occur Inside a Transformer?

While electrical and thermal failures often take the spotlight, mechanical faults in transformers are just as dangerous—often hidden, yet capable of causing catastrophic failure, internal arcing, core damage, and eventual breakdown. These faults result from physical stresses such as short-circuit forces, improper handling, or insulation shrinkage, and are especially difficult to detect without advanced diagnostic tools. Understanding and preventing mechanical faults is crucial for ensuring transformer safety, longevity, and performance.

Mechanical faults inside transformers typically involve core displacement, winding deformation, insulation compression, loose clamping, and structural damage caused by electromagnetic forces during short circuits, vibrations, thermal expansion, or poor transport handling. These faults compromise electrical clearances, increase dielectric stress, and often trigger secondary thermal or electrical failures. Detection relies on frequency response analysis (FRA), DGA trends, acoustic monitoring, and physical inspection.

This article examines the causes, consequences, types, and detection techniques of transformer mechanical faults—empowering operators to avoid undetected degradation and catastrophic collapse.

Mechanical faults such as winding movement, core displacement, and loose clamping can severely impair transformer performance and safety.True

These faults alter internal geometry, causing increased stress, insulation damage, and eventually triggering electrical breakdown.

Mechanical faults are impossible in sealed transformers and do not occur during normal operation.False

Mechanical faults can develop due to internal forces, transport vibration, thermal cycling, or short-circuit stresses, even in sealed units.


1. Winding Deformation or Displacement

Fault TypeDescription
Axial deformationWinding compresses or elongates vertically
Radial bucklingWindings deform inward or outward due to magnetic forces
Spiral twist or displacementCoils misalign or rotate under fault stress

Causes:

  • High fault current (short circuits)
  • Inadequate mechanical support
  • Thermal cycling causing insulation shrinkage

Risks:

  • Insulation cracking
  • Electrical clearance reduction → arc risk
  • Core imbalance → increased losses

Detection:

  • Frequency Response Analysis (FRA)
  • Sweep frequency measurements
  • Changes in leakage impedance

2. Core Displacement or Loosening

Fault DescriptionMechanical movement of laminated iron core
Misalignment of core stacksCan disturb magnetic symmetry
Loosened core clampsVibration, noise, and core heating

Causes:

  • Transportation impact
  • Short-circuit shock
  • Improper bolting or clamping torque

Risks:

  • Core vibration and audible noise
  • Eddy current losses
  • Core-to-ground short risk

Detection:

  • Audible noise increase
  • Infrared thermography (hot spots)
  • Electrical signature analysis

3. Insulation Compression and Degradation

Fault MechanismShrinking, crushing, or misalignment of insulation layers

Causes:

  • Thermal aging of paper insulation
  • Mechanical stress during tap changes
  • Oil contamination reducing elasticity

Risks:

  • Loss of dielectric separation
  • Paper turning brittle → partial discharge
  • Tap changer arcing and contact wear

Detection:

  • DGA indicating cellulose breakdown (CO, CO₂)
  • Tan delta or power factor test
  • Visual inspection (if unit is opened)

4. Loose Clamping and Structural Support Failures

ComponentTypical Fault Description
Winding clampsLose tension, leading to winding movement
Tie rods and press boardsCan shift, break, or shear under force
Radiators or external fastenersMay vibrate loose in high-load cycling

Causes:

  • Repeated thermal expansion cycles
  • Poor maintenance or original assembly
  • External shock or seismic events

Risks:

  • Escalates into winding displacement
  • Increases vibration and mechanical resonance
  • Shortens transformer lifespan

Detection:

  • Acoustic vibration monitoring
  • Periodic mechanical torque audits
  • FRA comparison with baseline

5. Tap Changer Mechanical Wear and Failure

TypeMechanical fault during tap shifting
Contact misalignmentImproper engagement of movable contacts
Gear and motor wearIncreased switching time, inconsistent operation

Causes:

  • Frequent load tap changes
  • Aging actuator motors
  • Inadequate lubrication or design flaws

Risks:

  • Arcing and carbonization
  • Thermal runaway at contact site
  • Voltage instability or incorrect output

Detection:

  • Tap changer signature analysis
  • Motor current curve deviation
  • Online tap position tracking

6. Handling and Transport Damage

ScenarioMechanical shock during installation or movement

Vulnerable Components:

  • Windings and core clamps
  • Bushings and oil conservators
  • Radiators and gaskets

Risks:

  • Unseen internal deformation
  • Future fault initiation under load
  • Warranty voidance and operational hazard

Detection:

  • Post-delivery FRA testing
  • Transport log review (shock sensors)
  • Visual inspection and torque checks

Summary Table: Common Mechanical Faults in Transformers

Fault TypeCauseDetection Tool(s)
Winding deformationShort-circuit forces, thermal expansionFRA, impedance tests, thermography
Core displacementHandling, loosened clampsAudible noise, thermography, signature analysis
Insulation collapseAging, shrinkage, stressDGA, tan delta, visual inspection
Clamping looseningVibration, torque lossVibration analysis, torque check
Tap changer wearOveruse, motor faultsMotion signature, oil analysis
Transport damageShock, drop, improper supportFRA, physical inspection, transport sensors

How Do Environmental Factors Contribute to Transformer Failures?

Transformers are designed to withstand extreme electrical and mechanical stresses—but environmental factors can silently degrade their performance and reliability. From temperature extremes and humidity to dust, pollution, wildlife, and UV exposure, the surrounding environment plays a critical role in accelerating aging, triggering insulation breakdown, and inducing mechanical and thermal stress. Ignoring these external conditions can lead to unexpected outages, fire risks, and premature transformer failure.

Environmental factors contribute to transformer failures by promoting insulation degradation, corrosion, moisture ingress, thermal stress, contamination, and wildlife interference. Key contributors include ambient temperature extremes, humidity, airborne pollution, ultraviolet (UV) exposure, salt spray, lightning, flooding, dust accumulation, and small animal intrusion. These factors can lead to tracking, flashover, overheating, or component failure if not properly mitigated.

This article explores in depth how different environmental elements affect transformer integrity, what failures they cause, and how to defend against them.

Environmental factors such as moisture, temperature extremes, pollution, and wildlife can directly lead to transformer failure.True

These conditions contribute to insulation breakdown, corrosion, contamination, and short-circuiting—major causes of transformer malfunction.

Transformers are immune to environmental conditions if they are installed outdoors.False

Even outdoor-rated transformers are susceptible to environmental stress without adequate protection, sealing, and maintenance.


1. Moisture and Humidity

EffectFailure Mechanism
Moisture ingress into insulationReduces dielectric strength, accelerates aging
Condensation inside tankCauses partial discharges, tracking, or arc
Hygroscopic behavior of paperAbsorbs water, loses mechanical integrity

Typical Consequences:

  • Breakdown voltage (BDV) drops
  • Paper insulation weakens and carbonizes
  • Increases partial discharge (PD) activity

Detection & Mitigation:

  • Dissolved Water-in-Oil (Karl Fischer) tests
  • Silica gel breathers, nitrogen sealing, air filters
  • Dehumidified enclosures or sealed conservators

2. Ambient Temperature Extremes

ScenarioImpact on Transformer
High temperatureAccelerates oil oxidation and insulation aging
Low temperatureIncreases oil viscosity, slows cooling circulation

Consequences:

  • Hot spot temperature >110°C → shortens insulation life
  • Cold oil can delay startup or damage bushings
  • Thermal expansion → seal leaks or mechanical stress

Mitigation:

  • Smart cooling systems (ONAF, OFWF)
  • Use of temperature sensors and alarms
  • Low-viscosity or synthetic insulating fluids for cold regions

3. Pollution and Airborne Contaminants

Contaminant TypeTypical SourceImpact
Salt sprayCoastal areasCorrosion, surface tracking
Industrial pollutantsCement, chemical, steel plantsAcidic or conductive deposits
Dust and sandDesert or arid zonesBushing contamination, flashovers

Consequences:

  • Leakage currents across insulators
  • Accelerated metal corrosion (clamps, bolts)
  • Increases surface conductivity → risk of tracking

Mitigation:

  • Anti-pollution bushings (creepage-extended)
  • Silicone coating or RTV insulation
  • Regular external washing and infrared scans

4. Ultraviolet (UV) Radiation

EffectTarget ComponentResult
UV exposure degrades elastomersGaskets, bushings, cable insulationCracking, embrittlement, leaks
Paint degradationTank and radiatorsCorrosion, heat absorption

Mitigation:

  • UV-resistant coatings and composite materials
  • Periodic repainting and gasket inspection
  • Indoor sheltering or sun-shielding enclosures

5. Lightning and Surges

CauseConsequence
Direct or nearby strikeOvervoltage → insulation flashover
Switching surgeVoltage spike damages winding insulation

Effects:

  • Bushing explosion
  • Tap changer flashover
  • Core saturation and dielectric failure

Protection:

  • Surge arresters with grading rings
  • Grounding grid integrity checks
  • Lightning shielding wires above transformer

6. Flooding and Water Ingress

ScenarioEntry PointResult
Flash flood or rising waterBase seal, cable glandWater intrusion, short-circuit risk
Stormwater in pit or trenchOil contamination, corrosionBreakdown of insulation properties

Prevention:

  • Elevated installation pads
  • Water-proof enclosures for connections
  • Flood drainage systems and moisture sensors

7. Wildlife Intrusion

AnimalCommon Faults Caused
RodentsChew cables, nest inside transformer tanks
BirdsNesting on bushings, cause shorting
Snakes and reptilesEnter cabinets → trigger phase-to-ground fault

Mitigation:

  • Wildlife barriers and vermin-proof mesh
  • Bushing covers and anti-nesting spikes
  • Sealed cable terminations

8. Seismic and Wind Events

EventStructural Impact
EarthquakeCore shifting, bushing cracking, anchor failure
High windsDislodging of radiators, bushings, or top accessories

Safeguards:

  • Seismic-rated design with bracing
  • Anchor bolt checks and dynamic loading analysis
  • Windbreak structures and fencing

Summary Table: Environmental Factors and Their Effects on Transformers

Environmental FactorKey ImpactRecommended Mitigation
Moisture/HumidityInsulation failure, PDBreathable seals, oil monitoring
Heat/Cold extremesAccelerated aging, poor coolingSmart cooling, temp alarms
Pollution/ContaminantsSurface tracking, flashoverRTV coating, insulator cleaning
UV RadiationMaterial degradationUV-resistant materials, shielding
Lightning/SurgesDielectric failureSurge arresters, proper grounding
FloodingOil contamination, shortsElevation, sealing, moisture detection
WildlifeChewed cables, shortsAnimal guards, mesh, insulation barriers
Wind/Seismic eventsMechanical deformationStructural reinforcement, anchoring

What Are the Signs and Symptoms of Impending Faults?

Even the most robust transformers exhibit early warning signs before failure occurs. These symptoms—if detected and interpreted in time—can prevent catastrophic faults, extend service life, and save costly downtime and repairs. Whether electrical, thermal, or mechanical in nature, impending transformer faults always leave behind measurable traces. Knowing what to look for is critical for predictive maintenance and operational safety.

The signs and symptoms of impending transformer faults include unusual noise, elevated oil and winding temperatures, abnormal dissolved gas levels, oil leaks, discoloration, bushing cracks, insulation resistance drops, irregular tap changer behavior, moisture contamination, and increased partial discharge activity. These indicators suggest issues like internal arcing, thermal aging, mechanical movement, or insulation failure—and should trigger immediate investigation.

This article explains each key symptom of transformer distress, the fault it likely indicates, and how to detect it before it escalates into an outage or fire.

Transformers exhibit detectable symptoms such as abnormal gas levels, overheating, noise, and oil leakage before failing.True

These signs often precede catastrophic faults and allow for preventive diagnostics and repairs.

Transformer faults occur suddenly without any early warning signs.False

Most transformer failures are preceded by measurable changes in temperature, gas generation, or electrical behavior that signal pending failure.


1. Unusual Noise or Vibration

SymptomPossible Fault
Humming louder than usualCore loosening, magnetostriction imbalance
Rhythmic knockingWinding movement or loose clamps
Sharp clicking or cracklingPartial discharges or contact arcing

Detection:

  • Acoustic sensors
  • Operator log reports
  • Vibration spectrum analysis

Sudden sound pattern changes often signal mechanical stress or internal sparking.


2. Oil Temperature and Winding Hot Spot Rise

IndicatorPotential Issue
Consistent top oil temperature above normalOverload, blocked radiators, cooling fan failure
Hot-spot reading exceeds thresholdWinding overloading or insulation breakdown

Detection:

  • Thermal sensors in oil and windings
  • SCADA real-time temperature alarms
  • Thermal modeling (IEEE/IEC methods)

Every 6–8°C rise in hot-spot temperature halves insulation life.


3. Dissolved Gas Analysis (DGA) Abnormalities

Gas DetectedAssociated Fault Type
Hydrogen (H₂)Corona or partial discharge
Acetylene (C₂H₂)Arcing or high-energy internal fault
Methane/Ethane (CH₄, C₂H₆)Overheating of oil or windings
CO, CO₂Cellulose insulation aging or overheating

Detection:

  • DGA lab testing
  • Online gas monitoring sensors
  • Key gas ratios (Rogers, Duval triangle)

DGA is the gold standard for identifying internal incipient faults.


4. Oil Leakage or Discoloration

Visual CuePossible Cause
Dark or cloudy oilContaminants, oxidation, carbonization
Oil dripping near sealsTank seal deterioration or expansion leaks
Wet spots around bushingsCapillary leakage or gasket failure

Detection:

  • Oil color test (ASTM D1500)
  • Daily inspection log
  • Moisture and dielectric breakdown testing

Oil condition directly reflects internal thermal and chemical events.


5. Bushing Surface Anomalies

SymptomRelated Fault
Cracks or chalkingUV degradation, thermal stress
Surface trackingPollution, moisture, or PD activity
Flash marks or burningArcing or surge event

Detection:

  • Visual inspection
  • IR scanning of bushing hotspots
  • Capacitance and power factor testing

Bushings are the entry point for most flashovers and failures.


6. Moisture Contamination

EvidenceCause and Risk
Low insulation resistanceWater ingress through seals or oil oxidation
High water-in-oil ppmBreather failure, humid environment
Condensation in conservatorCooling and heating cycles, improper design

Detection:

  • Insulation Resistance (IR) test
  • Karl Fischer titration
  • Relative humidity sensors

Moisture reduces dielectric strength and accelerates paper insulation aging.


7. Irregular Tap Changer Operation

SymptomFault Mechanism
Inconsistent voltage outputTap position not aligning or stuck
Arcing or burnt oil smellTap contacts degraded or carbonized
Motor takes longer to actuateMechanical wear or jamming

Detection:

  • Tap change counter analysis
  • Motion current signature tracing
  • Visual and oil inspection of diverter switch

Tap changers account for 30–40% of transformer failures.


8. Abnormal Load and Voltage Patterns

ObservationUnderlying Issue
Load imbalancePhase winding issue or feeder faults
Voltage dips or swellsRegulation failure or short-term fault

Detection:

  • Load profile recording
  • Voltage trend analysis
  • Fault recorders and DR relays

Load and voltage anomalies may precede internal short circuits or core saturation.


9. Partial Discharge (PD) Activity

IndicatorEarly Fault Area
UHF signal burstVoids or defects in insulation
PD over 1000 pCSign of serious internal degradation
Audible noise or ozone smellSurface PD on bushings or terminals

Detection:

  • UHF/TEV online PD sensors
  • Acoustic PD triangulation
  • PD trend analysis software

PD is the earliest detectable symptom of insulation deterioration.


Summary Table: Impending Transformer Fault Signs

SymptomPotential FaultDetection Method
Unusual noiseCore/winding movement, arcingAcoustic monitoring, visual observation
Elevated oil temperatureOverload, cooling failureThermal sensors, SCADA alerts
DGA abnormalitiesArcing, overheating, insulation breakdownGas chromatography, online DGA monitor
Oil discoloration/leaksOxidation, internal arcing, seal failureVisual check, oil test (ASTM/IEC)
Bushing defectsUV aging, tracking, surge stressIR scan, visual inspection, capacitance test
Moisture presenceSeal leakage, humid environmentKarl Fischer, IR test, silica gel color
Tap changer delay/failureContact wear, motor failureSignature analysis, maintenance inspection
Load or voltage instabilityPhase faults, winding defectsLoad logs, digital recorders
Partial discharge spikesInsulation voids or degradationPD analyzer, TEV/UHF/ultrasonic sensors

How Can Faults Be Diagnosed and Prevented?

Transformer faults are among the most costly and disruptive failures in any power system. Yet many of them—thermal breakdowns, dielectric failures, winding distortions, oil degradation, and core displacements—begin silently. Early diagnosis and proactive prevention can mitigate risk, extend transformer lifespan, and maintain grid reliability. With the advancement of diagnostic testing tools, online monitoring, and condition-based maintenance, transformer fault management has moved from reaction to prediction and prevention.

Transformer faults can be diagnosed using techniques such as Dissolved Gas Analysis (DGA), Frequency Response Analysis (FRA), infrared thermography, insulation resistance testing, partial discharge detection, and online monitoring systems. Preventive measures include proper cooling, routine testing, oil maintenance, surge protection, load management, and scheduled inspections. Together, these strategies detect faults early, isolate the cause, and prevent damage from escalating.

This article details the tools and strategies to diagnose and prevent faults in transformers—from routine field testing to advanced sensor-based monitoring and lifecycle management.

Transformer faults can be diagnosed using tools like DGA, FRA, thermography, and prevented through routine maintenance, monitoring, and surge protection.True

These diagnostic and preventive practices are industry-standard approaches to maintaining transformer health and reliability.

Transformer faults cannot be predicted or prevented and only occur suddenly.False

Most transformer faults develop over time and show measurable warning signs, which can be caught with appropriate diagnostic techniques.


1. Diagnostic Techniques for Fault Detection

A. Dissolved Gas Analysis (DGA)

Fault DetectedGases Produced
Thermal faultsCH₄, C₂H₆, C₂H₄
Arcing faultsC₂H₂, H₂
Insulation agingCO, CO₂
  • Tool: Online DGA monitors or lab kits
  • Use: Detect early-stage internal faults before physical damage occurs
  • Standard: IEEE C57.104, IEC 60599

B. Frequency Response Analysis (FRA)

ApplicationFault Detected
Winding movementDisplacement, deformation
Core issuesLoosened laminations
  • Tool: FRA sweep analyzer
  • Use: Post-fault or post-shipping structural assessment
  • Advantage: High sensitivity to minor mechanical faults

C. Infrared Thermography

Fault IndicationVisual Symptoms
Hot spots in bushingsThermal gradient anomalies
Loose connectionsOverheated terminals or joints
  • Tool: IR thermal cameras (handheld or drone)
  • Use: On-load heat signature mapping
  • Frequency: Quarterly or bi-annual scans

D. Partial Discharge (PD) Analysis

PD SourceCommon Fault Area
Surface trackingBushings, terminals
Internal voidsPaper insulation, winding defects
  • Tool: UHF sensors, acoustic detectors
  • Use: Detect incipient insulation breakdown
  • Detection: In pC or UHF dBµV (IEC 60270)

E. Insulation Resistance & Polarization Index

ParameterIndicates
Insulation Resistance (IR)Moisture, contamination
PI (IR\@10min / IR\@1min)Insulation aging
  • Tool: Megohmmeter
  • Use: Routine dielectric condition assessment
  • Threshold: PI < 2 suggests insulation degradation

2. Preventive Maintenance Strategies

A. Oil Maintenance and Filtration

ActionBenefit
Oil purificationRemoves moisture and gas
Regular BDV testingMaintains dielectric strength
Acid number monitoringTracks oxidation levels
  • Tool: BDV kits, DGA, moisture testers
  • Frequency: Every 6–12 months or condition-based
  • Standard: IEC 60296 oil specifications

B. Cooling System Inspection

ComponentFailure Mode
Radiators cloggedReduced heat dissipation
Fans/pumps not functioningThermal overload risk
  • Action: Verify coolant flow, fan switching, and oil circulation
  • Tool: IR scan, fan relay test
  • Interval: Monthly visual checks, quarterly load-run tests

C. Surge and Lightning Protection

DeviceFunction
Surge arrestersProtect against overvoltage from lightning
Shield wiresIntercept direct strikes
Grounding gridProvides safe fault current path
  • Action: Check arrester condition and grounding resistance
  • Tool: Earth tester, thermal imaging
  • Standard: IEEE 80, IEC 60099-4

D. Tap Changer Inspection and Oil Sampling

Fault RiskPrevention Action
Arcing or contact wearPeriodic inspection, oil filtration
Control motor wearTest switching cycles
  • Tool: Contact resistance tester, signature analyzer
  • Schedule: 5,000 to 10,000 operations or annually
  • Note: Tap changers are the most fault-prone mechanical component

3. Online Monitoring and Automation

Monitored ParameterBenefit
Oil temperature and loadDynamic rating and thermal alerting
DGA in real timeFault precursor detection
PD and vibration levelsAdvanced insulation and mechanical alerting
Tap position and motor runtimeCondition-based tap maintenance
  • Tool: Smart transformer monitors, IoT platforms
  • Integration: SCADA, cloud analytics, DERMS
  • Advantage: Enables real-time diagnosis and predictive action

4. Operational Practices That Prevent Faults

PracticeImpact on Reliability
Load balancingPrevents overheating in windings
Phase symmetry checksAvoids neutral shifts and current imbalance
Ground resistance monitoringMaintains fault dissipation path
Environmental protectionShields against moisture, dust, and animals
  • Tip: Combine routine logs with trend analysis for proactive insights

Summary Table: Transformer Fault Diagnosis and Prevention

Diagnostic ToolFaults DetectedPrevention Strategy
DGAArcing, overheating, insulation failureOil monitoring, load control
FRAWinding displacementTransport bracing, core clamping checks
IR ThermographyHotspots, poor coolingTightening, cleaning, fan/pump checks
PD AnalysisInsulation voids, trackingSurface cleaning, moisture control
Oil Quality TestsContamination, oxidationRegular filtration, sealing, moisture removal
Online MonitoringAll parameters in real-timePredictive maintenance, auto-alarming

Conclusion

Transformer faults can lead to major disruptions if not identified and addressed promptly. By understanding the typical failure modes and their underlying causes—whether electrical, thermal, mechanical, or environmental—operators can implement effective monitoring and preventive strategies. With proper diagnostics and maintenance, the risk of transformer failure can be significantly reduced, ensuring safer and more efficient power delivery.

FAQ

Q1: What are the most common faults in transformers?
A1: The most common transformer faults include:

Insulation failure

Overheating

Oil leakage

Winding short circuits

Core faults

Bushing failures

Tap changer malfunctions

These faults can lead to performance degradation, outages, or even catastrophic failure if not addressed.

Q2: What causes insulation failure in transformers?
A2: Insulation failure is often caused by:

Thermal aging due to excessive heat

Moisture ingress into the oil or windings

Electrical stress from overvoltage or surges

Contaminated or degraded insulating oil
This type of failure compromises dielectric strength and can lead to short circuits.

Q3: Why does transformer overheating occur?
A3: Overheating is typically caused by:

Overloading beyond rated capacity

Poor ventilation or cooling system failure

Blocked radiator fins or oil circulation issues

High ambient temperatures
Prolonged overheating accelerates insulation breakdown and component aging.

Q4: What leads to winding short circuits?
A4: Winding short circuits can result from:

Mechanical damage due to vibrations or movement

Insulation degradation over time

Manufacturing defects

Electrical transients or surges
Short circuits often cause severe local heating and can result in transformer tripping or permanent failure.

Q5: How can transformer faults be detected and prevented?
A5: Faults can be detected using:

Dissolved Gas Analysis (DGA)

Thermal imaging

Partial discharge monitoring

Insulation resistance testing
Prevention involves regular maintenance, condition monitoring, oil testing, load management, and ensuring proper cooling and grounding.

References

"Common Transformer Faults and Diagnostic Methods" – https://www.transformertech.com/common-transformer-faults – Transformer Tech

"Causes of Transformer Failures and Prevention Tips" – https://www.powermag.com/transformer-fault-causes – Power Magazine

"Typical Transformer Faults and Their Detection" – https://www.electrical4u.com/transformer-faults-causes – Electrical4U

"Transformer Fault Diagnosis Using Condition Monitoring" – https://www.researchgate.net/transformer-fault-diagnosis – ResearchGate

"Understanding Insulation Failures in Transformers" – https://www.sciencedirect.com/transformer-insulation-failures – ScienceDirect

"Energy Central: Transformer Reliability and Maintenance" – https://www.energycentral.com/c/ee/transformer-reliability-guide – Energy Central

"Smart Grid News: Transformer Health Monitoring" – https://www.smartgridnews.com/transformer-fault-detection – Smart Grid News

"PowerGrid: Strategies for Transformer Protection" – https://www.powergrid.com/transformer-fault-protection – PowerGrid

Tags:

Picture of Norma Wang
Norma Wang

Focus on the global market of Power Equipment. Specializing in international marketing.

Get Support Now

Get a Quote / Support for Your Project

  • Don’t worry, we hate spam too!