What Happens During a Short Circuit?

A short circuit is one of the most severe electrical faults a power system can experience. It occurs when an unintended connection allows current to travel along an unintended path with little or no electrical resistance. For transformers and power systems, this can lead to mechanical stress, overheating, and catastrophic failure if not managed correctly. Understanding the consequences and dynamics of a short circuit is essential for electrical engineers, operators, and maintenance personnel.


What Physically Happens in a Transformer During a Short Circuit?

Short circuits are among the most violent and dangerous events that can occur in power systems—and transformers, being critical grid components, are particularly vulnerable. When a short circuit occurs, the transformer experiences an instantaneous surge of current—many times its rated capacity—which can cause intense mechanical forces, magnetic stress, heating, and even internal arcing. If not properly designed to withstand these extreme conditions, a transformer can suffer catastrophic failure within milliseconds. Understanding the physical phenomena inside a transformer during a short circuit is essential for engineers, asset managers, and protection designers.

During a short circuit, a transformer experiences a rapid rise in fault current that produces intense electromagnetic forces acting on its windings. These forces can deform, displace, or collapse the windings if mechanical bracing is insufficient. The sudden current surge also causes extreme heat generation, possible insulation breakdown, and pressure waves that stress the core and tank. Internal arcing, dielectric fluid breakdown, and magnetic core saturation may occur. If not cleared promptly by protection systems, these effects can permanently damage the transformer or lead to explosion.

Short circuits produce purely thermal stress in transformers.False

Short circuits generate both thermal and intense mechanical forces due to magnetic field interactions.

Transformer windings can be physically displaced by fault currents.True

High electromagnetic forces during faults can bend or move windings, especially if they lack structural bracing.

Transformers must be designed to withstand dynamic short-circuit forces as per IEC 60076-5.True

Short-circuit withstand capability is a critical design requirement under international standards.


Electromagnetic and Mechanical Forces During Short Circuit

The most critical physical reaction in a transformer short circuit is the intense Lorentz force between current-carrying conductors.

Force TypeMechanism
Radial ForcePushes winding turns outward or inward, like a spring compression
Axial ForcePushes top and bottom windings away from each other or toward the core
Shear ForceAttempts to twist or slide windings laterally across each other

These forces are proportional to the square of the short-circuit current:

$$
F \propto I^2
$$

If short-circuit current is 20× the rated current, the resulting mechanical force is 400× greater than during normal operation.


Heating and Dielectric Stress

ParameterShort-Circuit Impact
Copper Losses (I²R)Increase exponentially, causing rapid temperature rise
Oil TemperatureCan rise 100°C or more in a few seconds
Insulation BreakdownDue to heat and partial discharges under high stress
Gas Generation (DGA)Fault gasses like acetylene and ethylene are rapidly produced

If thermal limits are exceeded, cellulose insulation chars, bubbles form, and dielectric breakdown may occur.


Structural and Core Reactions

ComponentPhysical Response
Core ClampsMay loosen due to vibration or magnetic shock
Tank WallsDeform or bulge if internal pressure surges from gas evolution
ConservatorOil surge may trigger Buchholz relay as internal arcing causes gassing
BushingsFlashover risk due to voltage transients and insulation degradation

In severe cases, the entire transformer may vibrate or hum violently due to sudden core magnetostriction under saturated conditions.


Sequence of Physical Events During a Typical Fault

Milliseconds (ms)Physical Event
0–1 msShort-circuit current spikes instantly (peak fault current)
1–5 msMagnetic fields induce strong forces on windings
5–10 msWinding support begins to flex or shift; oil heating begins
10–30 msArc flash or partial discharge may ignite in insulation gaps
30–100 msCore and tank vibrate; gas generation starts; Buchholz trips (if equipped)
100+ msIf not cleared, internal failure escalates into irreversible damage

Protection relays are typically set to detect and isolate faults within 30–100 ms to prevent structural damage.


Design Requirements to Withstand Short Circuits

IEC 60076-5 specifies short-circuit testing to ensure transformer resilience:

Design FeaturePurpose
Winding Bracing and ClampingPrevent radial and axial movement
Duct Spacers and Block SupportsResist magnetic pressure on winding stacks
Tank Pressure Relief DevicesRelease pressure from internal arcing
High-Grade Cellulose InsulationWithstand short-term thermal stress
Oil with High Dielectric StrengthResist flashover and support voltage gradients

Factory short-circuit withstand testing simulates worst-case events with fault currents injected under controlled conditions.


Data Table: Short-Circuit Effects Based on Transformer Size

Transformer RatingFault Current (typical)Radial Force per TurnShort-Circuit Duration Tolerance
1 MVA~15–20 kA~200 N~0.5 seconds max
10 MVA~25–30 kA~1000 N~0.25 seconds max
100 MVA~40–50 kA~2500–3000 N<0.1 seconds preferred

The magnitude of force increases quadratically with current and linearly with conductor length and proximity.


Case Study: Windings Deformed by Repeated Faults

In a 132 kV substation transformer, undetected line faults caused repeated short-circuit events. Initial protection failures allowed current to persist for over 200 ms on each occasion. Inspection revealed:

  • Axial compression of HV winding
  • Radial bowing of LV winding, evident from DGA and sweep frequency tests
  • Permanent displacement of leads and oil degradation

The unit had to be rewound at significant cost—highlighting that even “temporary” faults leave permanent scars.


What Are the Main Causes of Short Circuits in Power Systems?

Short circuits in power systems are sudden, high-current faults that bypass normal load paths—causing voltage collapse, equipment damage, and possible power outages. These faults are typically unintentional contacts between phases or between phase and ground. The root causes are diverse, ranging from environmental events like lightning and flooding to insulation failure, human error, and mechanical breakdown. If not identified and mitigated, short circuits can result in transformer damage, arc flash incidents, or cascading grid instability. Understanding the main causes is key to implementing effective protection and prevention strategies.

The main causes of short circuits in power systems include insulation failure due to aging or thermal stress, environmental events like lightning strikes or wildlife contact, mechanical damage from vibration or poor installation, contamination from moisture or dust, and operational errors such as miswiring or equipment misuse. These faults can occur anywhere along the network—from transmission lines to transformers, switchgear, and underground cables—and must be rapidly cleared by protective relays and breakers.

Short circuits only occur due to equipment failure.False

Short circuits can result from external environmental factors, human error, or foreign object contact—not just equipment failure.

Lightning is a common external cause of transmission line short circuits.True

Lightning strikes can bridge insulators or flashover lines, creating a low-impedance path between conductors or ground.

Contaminated or wet insulation increases the risk of flashover and short circuit.True

Moisture or pollution on insulating surfaces lowers dielectric strength, making flashover more likely.


1. Insulation Failure in Equipment

Component AffectedCause of Failure
Transformer windingsAging cellulose, overheating, partial discharge
CablesWater treeing, mechanical stress, UV exposure
Circuit breakersArc erosion, dielectric degradation
BushingsOil leaks, contamination, surface tracking

Once dielectric breakdown occurs, voltage surges or load current can force arcing between conductive parts—leading to a short.


2. Environmental Factors

SourceMechanism
Lightning StrikesHigh-energy impulse causes insulation flashover
Flooding or Water IngressCauses insulation breakdown in cables and switchgear
Windborne DebrisBrings conductive material into contact with phases
Pollution and DustForms conductive paths on insulators, especially with moisture

Outdoor insulators and unsealed enclosures are highly vulnerable in coastal, industrial, or rainy environments.


3. Wildlife and Vegetation Intrusion

Intrusion TypeEffect
Birds or SquirrelsBridge live conductors or short phase-to-ground
Tree BranchesContact energized lines, especially in storms
Nesting or ChewingDamages cable jackets or blocks venting in equipment

Utilities often install wildlife barriers and tree-trimming programs to mitigate these common, yet often overlooked, causes.


4. Mechanical Damage or Wear

EquipmentDamage Mechanism
Transformer windingsMovement under short-circuit stress, vibration fatigue
Switchgear contactsMisalignment, arcing, or pitting
Underground cablesExcavation hits or vehicle crush damage
Overhead linesConductor slap or broken crossarms

Even micro-vibrations can gradually degrade components, particularly in wind-prone or seismic areas.


5. Operational or Human Error

Error TypeConsequence
Incorrect wiringCross-phase connections or live-ground miscontact
Inadequate maintenanceIgnoring partial discharge or bushing oil leaks
Bypassing interlocksEnergizing circuits under unsafe conditions
Improper installationLoose joints, inadequate clearances, over-torquing

Human mistakes often trigger latent defects to evolve into full short-circuit conditions.


6. Aging Infrastructure

ComponentAging Effects
TransformersInsulation breakdown, moisture ingress
SwitchgearContact resistance, arc erosion
Protection relaysSlow operation or failure to trip
Conductors and jointsOxidation, fatigue, loss of mechanical strength

Legacy systems lacking modern insulation or monitoring are more prone to faults over time.


Real-World Example: Substation Short Circuit Due to Floodwater

  • Location: Urban 33/11 kV substation
  • Cause: Heavy rainfall flooded the control room
  • Fault Path: Water entered LV switchgear panel through floor conduit
  • Result: Earth fault caused busbar flashover and cascading outage
  • Remedy: Replaced affected switchgear, added cable sealing, installed water detection alarm

This underscores the importance of environmental design in substation layout and cable routing.


Visualization of Common Short-Circuit Causes

Cause CategoryVisual Risk Indicator Examples
Insulation failureBurn marks, tracking paths, abnormal DGA values
Lightning surgeMelted surge arresters, punctured bushings
Wildlife intrusionFeather/fur residue, dislocated terminals
Moisture contaminationWater pooling in cabinets, cloudy oil
Operational mistakesMismatched cables, unmarked terminations

Routine inspection and predictive maintenance tools like thermography, partial discharge monitoring, and insulation resistance tests can preempt many of these faults.


What Are the Effects of a Short Circuit on Transformer Performance?

A short circuit is one of the most severe electrical faults a transformer can experience. It leads to sudden and massive electrical currents, unleashing intense mechanical, thermal, magnetic, and dielectric stresses on the transformer’s internal components. Even if the fault is cleared quickly, residual damage can impair future performance—causing reduced insulation life, compromised mechanical integrity, or inefficient operation. In some cases, the effects are immediately catastrophic; in others, degradation occurs progressively, leading to latent failure years later. Therefore, understanding these effects is critical for determining post-fault transformer usability and ensuring long-term grid reliability.

A short circuit causes significant degradation in transformer performance by inducing mechanical deformation of windings, thermal damage to insulation, and dielectric stress that can lead to partial discharges or arcing. These impairments reduce the dielectric strength, increase internal losses, cause noise and vibration, and may shift impedance characteristics. Over time, the transformer becomes less reliable, prone to overheating, and may exhibit a higher failure rate unless thoroughly inspected, tested, or refurbished.

A short circuit only affects transformer performance during the fault duration.False

Even after a fault is cleared, permanent physical and dielectric damage can impair transformer performance long-term.

Deformation of windings after a short circuit can shift the transformer's impedance.True

Mechanical displacement of coils alters magnetic coupling and leakage paths, which affects impedance and regulation.

Short circuits reduce insulation life, even if protection systems act quickly.True

Thermal and dielectric stress during faults contributes to insulation aging and loss of mechanical resilience.


Immediate Effects of Short Circuit on Transformer Internals

ComponentDamage MechanismPerformance Impact
WindingsElectromagnetic compression, torsion, or bulgingImpedance changes, hot spots, weakened mechanical bracing
InsulationThermal shock, partial discharge, breakdownReduced dielectric margin, increased risk of future faults
Core & ClampsVibrations, loosening, localized saturationAudible noise, core losses, harmonic distortion
Cooling OilRapid heating, bubble formation, gas evolutionReduced cooling, altered dielectric properties
Tank & SealsInternal pressure rise, possible deformationOil leaks, misalignment, loss of nitrogen blanket

Even a transient fault lasting <100 ms can initiate slow degradation of multiple components.


Long-Term Performance Effects After a Short Circuit

Area AffectedResulting Performance Issue
Thermal ManagementHot spots due to displaced conductors or varnish delamination
EfficiencyHigher no-load and load losses due to winding displacement
Load Handling CapabilityReduced because of reduced insulation coordination
ReliabilityIncreased risk of failure under future switching or load surges
Acoustic EmissionsLouder hum or vibration from loosened core or clamp shifting

Transformers that survive short circuits without immediate failure may still fail prematurely due to hidden weakening of their insulation or structure.


Measurable Post-Fault Indicators

Diagnostic MethodWhat It Reveals
Sweep Frequency Response Analysis (SFRA)Detects core and winding displacement
Dissolved Gas Analysis (DGA)Indicates oil degradation and presence of arc or thermal gases
Power Factor/Tan Delta TestingReveals insulation aging or moisture ingress
Winding Resistance TestShows contact or joint damage
Impedance MeasurementIdentifies winding movement or shorted turns

These tests are often used during post-fault investigations to determine if a transformer can return to service or requires repair.


Short Circuit Impact Table by Duration and Intensity

Short-Circuit DurationPeak Fault CurrentTypical EffectsTransformer Impact
<10 ms (cleared instantly)20–30 × InMinor stress, no physical damage if robustUsually safe to return to service
10–100 ms20–40 × InElectromagnetic and thermal stress beginsMay require inspection, especially large units
100–500 ms30–50 × InInsulation damage, winding displacementThorough testing required
>500 ms50 × In and upSevere arcing, insulation collapse, fire riskLikely total failure

Prompt clearing by protection relays is essential to prevent long-term damage.


Simulation: Winding Shift and Impedance Change

In a 63 MVA transformer that underwent a 120 ms fault, the following post-fault data was collected:

ParameterPre-FaultPost-FaultDeviation
Leakage Impedance (Z%)10.8%12.3%+14%
Load Loss at 75°C72 kW81 kW+12.5%
No-Load Current0.25%0.32%+28%
SFRA Peak ShiftBaseline-18 dB at 2 kHzIndicates winding movement

This confirms how minor deformation impacts energy efficiency and performance.


IEC Standards on Short Circuit Withstand Performance

IEC 60076-5 outlines design and test requirements:

RequirementStandard Expectation
Short-circuit withstand timeTypically 2 seconds for medium power transformers
Peak withstand currentMust survive up to 2.5 × rated symmetrical current
Mechanical bracingMust resist axial and radial forces
Testing methodHigh-current injection or synthetic testing

Transformers are tested at the factory for theoretical maximum stresses, but real-world system faults can exceed expectations.


Recommendations After a Short Circuit Event

ActionPurpose
Immediate Oil SamplingCheck for arc gases and moisture
Visual Inspection (if openable)Look for bushing or lead displacement
Electrical Testing SuiteEvaluate resistance, capacitance, insulation
Mechanical Integrity CheckVia SFRA or core clamp inspection
Load DeratingTemporarily limit loading until full clearance

Never re-energize a transformer after a major fault without testing, even if it looks outwardly intact.


How Are Transformers Protected Against Short Circuits?

A transformer is one of the most valuable and critical assets in a power system. Despite robust design standards, no transformer is immune to the dangers of a short circuit—either internally due to winding faults or externally from system conditions. When a short circuit occurs, the transformer's thermal and mechanical limits can be exceeded in milliseconds, leading to catastrophic insulation failure, tank rupture, or even explosion. That's why transformer protection is not optional—it’s an integrated system of devices and logic designed to detect, isolate, and report faults faster than damage can occur. These protection systems must be carefully selected, tested, and calibrated according to the transformer's rating, system configuration, and fault profile.

Transformers are protected against short circuits using a combination of differential protection relays, overcurrent and earth fault protection, Buchholz relays (for oil-filled units), surge arresters, pressure relief devices, and circuit breakers. These systems rapidly detect abnormal current, voltage, or internal gas generation, and isolate the transformer from the power grid before damage escalates. Protective devices are coordinated to act within milliseconds, adhering to IEC and IEEE standards to prevent thermal or mechanical failure during faults.

Differential relays can detect both internal and external short circuits.False

Differential relays detect internal faults only; external faults are handled by overcurrent or distance relays.

The Buchholz relay protects oil-filled transformers from internal arcing and gas buildup.True

It detects gas formation and oil surge due to internal faults and trips the transformer.

Circuit breakers must trip fast enough to prevent winding deformation during a short circuit.True

Delays in breaker operation can allow mechanical damage from high fault currents.


Primary Short Circuit Protection Systems for Transformers

Protection DeviceFunction
Differential Relay (87T)Detects internal phase-to-phase and phase-to-ground faults by comparing primary and secondary current
Overcurrent Relay (50/51)Trips for high fault current levels, usually for external faults
Ground/Earth Fault Relay (50N/51N)Detects asymmetry indicating phase-to-ground faults
Buchholz RelayMonitors internal faults via gas detection and oil movement (for oil-immersed units)
Surge ArresterProtects against transient overvoltages due to lightning or switching
Pressure Relief DeviceVents high-pressure gas in case of internal arcing or oil breakdown
Temperature RelaysTrip on excessive winding or oil temperature indicating stress

These elements are often connected to SCADA systems for remote fault indication and event logging.


Core Protection Principle: Differential Protection (87T)

Differential protection is the most critical and sensitive method for transformer short circuit protection.

Measurement LogicOutcome
Current In = Current OutNo internal fault, normal state
Current In ≠ Current OutInternal fault, initiate trip

Differential current:

$$
I{\text{diff}} = I{\text{primary}} - \text{CT ratio} \cdot I_{\text{secondary}}
$$

If the differential current exceeds a set threshold and is sustained for a defined time (e.g., >30 ms), the relay sends a trip signal to the circuit breaker.


Protection Coordination and Tripping Sequence

Time (ms)Protective Action
0–1 msFault occurs; CTs begin to sense imbalance
1–10 msDifferential relay processes data; compares phase currents
10–30 msRelay confirms internal fault; sends trip command to breaker
30–60 msCircuit breaker opens; transformer is isolated
60–300 msBuchholz relay may activate if gas is forming or oil surges occur

Speed is critical: Most mechanical damage during a short circuit happens within 50–100 ms.


Secondary and Backup Protections

Device/LogicPurpose
Time Overcurrent RelayActs as backup if differential relay fails or misses the fault
Restricted Earth Fault (REF)More sensitive than general earth fault protection
Distance Relay (for connected lines)Provides backup for zone-2 faults beyond transformer
Breaker Failure ProtectionEnsures transformer is isolated even if primary breaker fails
Alarm and Trip RecordersLogs sequence of events for diagnostics

These systems work in tandem to ensure no fault goes undetected or unaddressed.


Mechanical and Thermal Fault Indicators

For oil-immersed transformers, non-electrical protective devices also provide critical safety margins:

DeviceActivation ConditionAction Taken
Buchholz RelayDetects internal gas, oil surgeTrips transformer
Pressure Relief ValveHigh-pressure surge in tankVents gas, sends alarm
Oil Level RelaySudden drop in conservator levelTriggers alarm or trip
Winding Temp SensorExcessive thermal riseInitiates cooling or trip

All signals are wired to lockout relays that can prevent re-energization until inspection is completed.


Protective Device Mapping in an Example 132/33 kV Transformer

Protection FunctionDevice CodeHardware LocationRelay Brand (Example)
Differential Protection87TMain relay panelSEL 787 / ABB RET670
Buchholz RelayTop of main tank (inline)MESSKO / Qualitrol
Overcurrent (HV & LV)50/51Feeder panelSiemens / Schneider
Earth Fault50N/51NNeutral grounding systemGE Multilin / ZIV
Temperature Relay49Control cabinetRishabh / ABB
Pressure Relief ValveTank top or coverExplosion-proof spring

These form a complete protection architecture governed by IEC 60255 and IEEE C37 series standards.


Performance Chart: Fault Clearing Time vs. Transformer Damage Risk

Fault Clearing TimeDamage PotentialAction Taken
<50 msMinimalProtection relay fully effective
50–100 msMediumMechanical stress possible
100–300 msHighWinding displacement, insulation aging
>300 msCriticalPermanent damage, oil fire risk

Prompt tripping preserves the mechanical and dielectric integrity of the transformer.


Conclusion

A short circuit represents a high-risk event in any electrical system, particularly for vital assets like power transformers. If not swiftly interrupted, it can cause irreversible damage to windings, insulation, and the transformer core. Comprehensive protection systems, regular maintenance, and robust design are essential to minimize risk and ensure transformer reliability under fault conditions.


FAQ

Q1: What exactly is a short circuit in a transformer?
A1: A short circuit occurs when there is an unintended low-resistance path between conductors, causing excessive current flow. In a transformer, this can happen:

Internally: between winding turns or phases

Externally: in connected cables or equipment
This sudden surge can be many times the rated current, potentially causing severe thermal and mechanical stress on the transformer components.

Q2: What are the immediate effects of a short circuit?
A2: When a short circuit occurs, it leads to:

Massive overcurrent (often 10–25 times nominal current)

Rapid heating of windings and conductors

Mechanical deformation of windings due to magnetic forces

Voltage drops or outages in the electrical system

Triggering of protection systems like circuit breakers or relays
If not cleared quickly, it can cause permanent damage or explosion.

Q3: What transformer components are most vulnerable?
A3: The components most affected by short-circuit forces include:

Windings: Can deform or burn due to heat and magnetic forces

Core insulation: May break down, causing internal arcing

Tap changers: Prone to contact welding or damage under fault currents

Bushings and terminals: Subject to flashover or thermal cracking
Repeated or high-energy short circuits shorten the transformer's lifespan significantly.

Q4: How do protection systems respond to a short circuit?
A4: Transformers are protected using:

Differential relays: Detect imbalances in current

Overcurrent relays: Trip circuits at preset limits

Buchholz relays (in oil-immersed units): Detect gas or pressure changes

Circuit breakers or fuses: Interrupt current flow within milliseconds
These systems are designed to isolate faults quickly, minimizing damage and fire risk.

Q5: Can a transformer be reused after a short circuit event?
A5: That depends on the severity. After a short circuit:

The transformer undergoes electrical and mechanical inspections

Tests include winding resistance, insulation resistance, and SFRA

Minor faults may be repairable (e.g., bushing or tap changer replacement)
Severe damage—like winding collapse or core shift—often requires full rewinding or replacement. Post-fault diagnostics are essential before re-energization.

References

Electrical4U: Short Circuit in Transformer
https://www.electrical4u.com/short-circuit-test-of-transformer/

IEEE C57.109-2018: Guide for Transformer Short Circuit Withstand
https://standards.ieee.org/standard/C57_109-2018.html

Doble Engineering: Post-Fault Diagnostic Testing
https://www.doble.com/solutions/fault-analysis-and-testing/

NREL: Transformer Reliability and Fault Tolerance
https://www.nrel.gov/docs/fy21osti/transformer-short-circuit-failure.pdf

ScienceDirect: Mechanical and Thermal Effects of Short Circuits in Transformers
https://www.sciencedirect.com/science/article/pii/S0378779619303525

Tags:

Picture of Norma Wang
Norma Wang

Focus on the global market of Power Equipment. Specializing in international marketing.

Get Support Now

Get a Quote / Support for Your Project

  • Don’t worry, we hate spam too!